§ 13.08.050. Addition to Section 903.1.2—Fire control room.  


Latest version.
  • Add the following as Section 903.1.2, fire control room:

    Fire Control Room. In all buildings in which automatic sprinklers are installed, a room shall be provided separating all sprinkler risers, fire alarm control panels and equipment from the remainder of the building. The separation shall consist of sheet rock or fencing material with the height of at least eight feet fully enclosing and separating the room. Increased separation may be required by the fire chief or his designee. Access from the inside of the building shall be limited and only installed at the discretion of the Fire Chief or his designee. The Fire Control Room shall be provided with an exterior door access for fire department use.

(Ord. No. 2682, 6-14-10)